Ampd Energy · IEC variant · Rev 1.3, 29 April 2026

Ampd 400

A mobile battery energy storage system made by Ampd Energy, for demanding construction and industrial sites. The larger unit, with double the nominal output and nominal DC capacity of the Ampd 200. It is typically considered for heavier or longer duties.

Nominal output
386kW
428 kVA
Nominal DC energy
430kWh
Rated capacity, not usable AC energy
Peak, up to 10 seconds
585kW
Overload rating, time-limited
Maximum charging input
410kW
Unit limit, not site supply

Where it is considered

  • Larger tower cranes, or more than one crane or hoist on a shared supply
  • Bigger construction sites with sustained plant loads
  • Industrial equipment with high starting currents
  • Longer periods between charging opportunities

What an assessment checks

  • That sustained demand stays within nominal output, with peaks inside the overload durations
  • Ambient conditions against the listed operating range and derating point
  • The charging supply actually available on site
  • Access and lifting for a unit of up to 9,000 kg

Suitability is a judgement about your load, supply and site. It is made in a technical assessment, not from a specification table.

Output ratings and their durations

The Ampd 400 sustains its nominal output. Above that it has two overload ratings, each limited in time. The brochure does not set out the conditions for repeated overloads, so a duty with frequent peaks is checked by an engineer.

Nominal output386 kW / 428 kVA
Overload, up to 60 seconds466 kW / 496 kVA
Overload, up to 10 seconds585 kW / 595 kVA
Nominal: the sustained rating Overload: time-limitedBars share one kW scale. Ampd 400 IEC brochure, Rev 1.3, dated 29 April 2026.

Specifications

Ampd 400 IEC Rev 1.3: specifications
SpecificationAmpd 400IEC · Rev 1.3 · 29 April 2026
Output
Nominal output power386 kW / 428 kVA
Nominal output current at 380 / 400 / 415 Vac650 / 618 / 595 A
Overload output, up to 60 secondsTime-limited rating, not continuous output.466 kW / 496 kVA
Overload current, up to 60 seconds, at 380 / 400 / 415 Vac754 / 716 / 690 A
Overload output, up to 10 secondsTime-limited rating, not continuous output.585 kW / 595 kVA
Overload current, up to 10 seconds, at 380 / 400 / 415 Vac904 / 858 / 827 A
Energy storage
Rated nominal DC capacityNominal DC capacity. Usable delivered AC energy is lower and is confirmed per project.430 kWh
Battery cell typeCATL lithium iron phosphate (lfp)
Rated battery cell lifeCell rating. The brochure states it does not equal warranted cycles.9,000 cycles
Charging input
Maximum charging powerUnit limit. Actual charging depends on the supply available on site.410 kW
Maximum charging current at 380 / 400 / 415 Vac624 / 593 / 571 A
Electrical
Voltage range380 to 415 Vac (3Ph + N + PE)
Frequency, as printed50 / 60 ± 2.5 Hz
Generator integration
Supported configurationAmpd 400 connected with 1 generator
Microgrid controller compatibilityComAp or DeepSea
Recommended maximum generator capacityA recommended maximum, not a minimum or default generator size.650 kVA
Mechanical
Ambient operating temperature−20 to +50 °C (derating from 45 °C)
Dimensions (L × W × H)3.0 × 2.3 × 2.4 m
Maximum wet weightActual weight depends on the optional features fitted.9,000 kg
Ingress protection: batteries and HVACIP67
Ingress protection: container enclosureIP54
Corrosion protection (standard)C3
Other
Fire suppression systemAerosol agent
Thermal management and coolantLiquid cooled, ethylene glycol
ConnectivityCellular 4G
Warranty durationDuration only. Warranty terms and any warranted throughput are confirmed in a proposal.5 years

Source: Ampd 400 IEC brochure, Rev 1.3, dated 29 April 2026. Manufacturer-published figures for the IEC variant, not independently tested. Specifications can change, so the current data sheet for your territory is confirmed in a project proposal. Document 760-00017, page 2.

Optional equipment

None of the following is part of the standard specification. Each is fitted only when specified, and affects weight and applicable certifications.

OptionAs listedStandard fit?
Serial charging systemRated power of the optional serial charging system. Separate from the main charging input.40, 80 or 120 kWNo, optional
Direct DC MPPT controllerFor direct DC solar input. Applies only when the option is fitted.60 kW (input voltage up to 900 Vdc)No, optional
Power interconnect optionsPowerlock, CamlockNo, optional
Enhanced corrosion protectionStandard corrosion protection is C3.C4No, optional

Certifications as listed

These are the entries in the brochure, with their scope. They are listings, not certificates: the documents for a specific configuration are obtained as part of a project.

System level
  • IEC 62040-1
Power electronics
  • IEC 62477-1
  • IEC 61851-1: Units equipped with serial chargers only
  • IEC 61851-23: Units equipped with serial chargers only
  • IEC 62109-1: Units equipped with MPPT controllers only
EMC
  • IEC 61000-6-2
  • IEC 61000-6-4
  • IEC 62040-2
Battery
  • IEC 62040-1
  • IEC 62619
  • UL 9540A (cell): Cell-level test listing. The brochure does not list UL 9540 system certification.
Transportation
  • UN 38.3 (road and sea)

Where published sources differ

The brochure and the manufacturer’s product web page, as reviewed on 2 October 2026, give different values for two items. This page uses the brochure values for Rev 1.3. Which applies to a supplied unit is confirmed with current documentation in your proposal.

ItemBrochure Rev 1.3Manufacturer web pageStatus
Container enclosure protectionIP54Up to IP55Unresolved; confirmed per project
Maximum ambient operating temperature+50 °CUp to +55 °CUnresolved; confirmed per project

Manufacturer statements

  • “Up to 90% reduction in carbon footprint”

    Manufacturer statement, compared to generators of similar capacity. Not a forecast for a particular site.

A battery discharging on site produces no exhaust there. Overall emissions depend on how it is charged: a battery charged by a diesel generator is not zero-emission power.

Ampd 400 questions

What is the continuous output of the Ampd 400?

The Ampd 400 IEC brochure (Rev 1.3) lists a nominal output of 386 kW / 428 kVA. Its higher figures are overload ratings: 466 kW / 496 kVA for up to 60 seconds, and 585 kW / 595 kVA for up to 10 seconds. They are time-limited and are not continuous output.

How long will the Ampd 400 run?

Runtime depends on your load. The brochure lists 430 kWh of rated nominal DC capacity, which is not the same as usable AC energy delivered to your equipment. Usable energy, losses and reserve are confirmed in a project assessment.

Is the 9,000-cycle figure a warranty?

No. It is the rated life of the battery cells, where a cycle is one full charge and full discharge. The brochure states that rated cycle life does not equal warranted cycles. The listed warranty duration is 5 years; the full terms are confirmed in a proposal.

Can the Ampd 400 be used in the United States or Canada?

The published data covers the IEC variant for 380 to 415 Vac supplies. Its 50 / 60 Hz entry does not establish a North American voltage variant, and the brochure lists UL 9540A at cell level only. The applicable variant and approvals are confirmed for each North American project.

Tell us about the site for a project-specific proposal

A short brief is enough to start. “Not sure” is an acceptable answer to every technical question, and you see a summary of your project before you add any contact details.